GCK low-voltage draw out type switch cabinet is widely used in power plant, substation, factories and high-rise building power distribution center PC and motor control center MCC, as AC 50-60Hz, rated working voltage to 660V and below, rated current 4000A and below the hair, power supply system in power distribution, motor control, without the use of reactive power compensation of low-voltage power distribution device.
Rated insulation voltage: AC 660V, AC 1000V
Rated operating voltage: AC 380 V, AC 660 V
Rated frequency: 50Hz
The maximum current of the feed circuit: 3150A
Drawer circuit maximum current: 3150A
Control motor maximum capacity: 320KW
Peak withstand current (0.1S):63KA, 105KA, 176KA
Short time withstand current (1S) of horizontal busbar: 30 KA, 50 KA, 80 KA, 100 KA
Vertical bus peak withstand current (0.1S): 63 KA, 105 KA
Short time withstand current of vertical bus (1S): 30 KA, 50 KA
Rated power frequency withstand voltage (1min): 2500V
Two power frequency withstand voltage (1min): 2500V
Protection level: IP30, IP40
*800 (1000) mm:600 (1000) *2200 (800) with wide shape and wide * depth *